Process Safety · Case study

Buncefield, 2005: filling blind

A petrol storage tank overflowed for about 40 minutes because both its level protections had failed. The vapour cloud exploded.

Date11 Dec 2005
WhereBuncefield oil depot, Hemel Hempstead, UK
ReleasedAbout 300 t of petrol
DeathsNone
Injuries43
FireBurned for about 5 days, 20+ tanks

What happened

Tank 912 was being filled with unleaded petrol from a pipeline overnight. Its automatic level gauge had been sticking intermittently since a service in August, and on that night it stuck, showing a constant level while the tank kept filling. The independent high-level switch, which should have shut off the flow, was inoperative: a test lever had not been put back in place after testing.

Petrol cascaded over the tank roof, broke up into droplets and evaporated, forming a large vapour cloud in still, cold air. At 06:01 it ignited, causing a vapour cloud explosion far more violent than expected and the largest fire in peacetime Europe.

Sequence of events

~19:00 (10 Dec)Tank 912 starts receiving petrol.
~03:00The level gauge sticks; the reading stays flat.
~05:20The tank is full; the high-level switch does not trip. Petrol overflows.
06:01The vapour cloud ignites: explosion, then fire across the site.

Why it happened

Lessons for your plant

Learn more on PharmaChemE

Sources

Summary written for training. Figures are as published by the investigating bodies and widely cited sources; see the sources for full details.